04 Try it yourself Interactive
The same four media and the same 20 dB budget as section 02. Choose a medium and a run length, then step through the calculation one line at a time: the attenuation coefficient, the total loss over the run, how far a single segment reaches, and finally how many regenerators the run needs. The four counters are computed from the figures on screen, so every number is arithmetic you can redo on paper.
The loss coefficients are approximate and deliberately labelled as such. Real cable comes with a frequency-dependent insertion loss curve from its manufacturer, and real fibre is specified per wavelength window. These are honest order-of-magnitude figures for the conditions named beside each one, chosen because the conclusions they produce match reality: 20 dB on Cat 6 lands on exactly the 100 m that structured cabling standards allow, and 20 dB on single-mode fibre lands on the 100 km that submarine amplifier spacing is actually built to. Connector and splice losses are left out so that only one variable moves. Nothing plays on its own: Next, Back and Reset, or the arrow keys.